Product Profile of Auto Mains Failure Panels
Ambika Enterprises manufactures Auto Mains Failure Panels. Ambika Enterprises supplies a vast range of electronic drawout and non drawout Control panels. The Auto Mains Failure Panels have in-built safety features for protecting the Engine and alternator and are applicable for managing DG sets.
Key Features of Auto Mains Failure Panels
- A power circuit consisting of contactor, MCB and fuses.
- Automatic start/stop of the genset in case of AC mains failure and its restoration respectively.
- Manual start/stop facility also provided.
- Mains Failure: 3-attempt engine cranking after mains failure
- Unhealthy Mains: Any of the phase failure or voltage drops below set value.
- Mains Restoration: Engine keeps running for 30 seconds before stopping
- Metering: One Ammeter with CTs and selector switch, one frequency meter, one voltmeter with selector switch and one hour meter.
- Set of indications: Load on DG, mains, Fault indications, LLOP, High water temp/high cylinder head temp and Overload.
- Set of Push Buttons: Engine start/stop, Alarm acknowledge button for hooter and Reset button for fault indication.
- Safety: High water temperature, LLOP, Overload trip.
- A separate battery charger for continuous charging of batteries in trickle/boost mode to ensure prompt starting of the engine.