Product Profile of Blood Refrigerator Controller With Digital Display
Blood Refrigerator Controller with Digital Display enables Calibration Error correction by front key switch without any presetting. The Blood Refrigerator Controller has the facility of Defrost Cycle start temperature. The Blood Refrigerator Controller works on supply voltage of 100-260 VAC. Blood Refrigerator Controller with Digital Display enables temperature to be adjusted in the range of -99.9 ° C to 100.° C
Key Features of Blood Refrigerator Controller With Digital Display
- Four digit, dual display
- Supply 100-260 VAC
- Input: RTD PT100
- Output: 1. Relay Contact or SSR, 2. Alarm contact or Buzzer
- On/Off Control action
- Cooling Application
- Range: -99.9 to 100.° C
- Accuracy of 0.5% of full scale
- Temperature As per range adjustable in set mode.
- Alarm High 0.3 to 10.0 adjustable
- Alarm Low 0.3 to 10.0 adjustable
- Alarm mute by Decrement key
- Hysteresis 0.2 to 25.° C adjustable
- Delay 0 to 100 minute adjustable for compressor
- Open display if Sensor break
- Relay trip if sensor breaks, connection open
- Calibration Error correction by front key switch (No preset setting)
- Configure link at Back terminal to avoid unauthentic entry.
- Defrost Cycle start temperature adjustable
- Defrost On time 0 to 250 Minute
- Defrost Off time 0 to 9999 Minute
- Defrost on indication by DP blinking
- Defrost on time countdown indication (Double display)
- Defrost on time countdown indication by Enter key(Single display)
- Manual defrost by pressing increment key for 5 second
- RS485 output Optional