Product Profile of Cell Environmental Systems
CP Engineering offers Cell Environmental Systems [CAHU P.T.H]. CP Engineering also offers Instrumentation and Measurement, Cell Environmental Systems, In-Cell Equipment and Dynamometers. The Cell Environmental Systems [CAHU P.T.H] are used to generate and replicate various atmospheric conditions and simulate different altitudes from the available ambient air supply.
Key Features of Cell Environmental Systems
- It is able to monitor and adjust pressure, temperature and humidity.
- The Air filter is used to filter out any large particulates from the air supply prior to entry into the CAHU cooling coil.
- The cooling coil is fed with chilled water or water/glycol at a fixed rate. The cooling coil is used to cool the in-cell air.
- The Humidifier is used to add steam, and hence increase the humidity
- The steam is introduced to the process air with a Steam Lance.
- The heater battery consists of a number of heating elements, [typically 3x2kW elements] which can be switched on to give four combinations [0,2,4,6kW] to heat the air passing over them.
- Air flow is created using a fan. The fan is capable of raising the combustion air pressure by approximately 120mBar [12kPa] above the air inlet pressure. This fan has a separate 4kW motor and is belt driven.
- A Secondary cooling Coil is used to remove any heat added by the action of the fan on the air, this is fed with a chilled water supply
- Can be manually controlled using a hand operated by-pass valve.